Loss reduction in port harcourt 33/11kv distribution networks by power factor correction

Authors

  • Omorogiuwa Eseosa University of Port Harcourt, Rivers State, Nigeria
  • Kesiena Mik University of Port Harcourt, Rivers State, Nigeria

Keywords:

Apparent power, Distribution network, Power factor correction, Power world simulator, Reactive power

Abstract

Poor power factor often results in high losses of active power in the network. It measures the percentage of apparent power that can be used to do actual work by the loads. However, this result in a reduction of systems reliability and creates safety problems and a much-increased energy cost. These inductive loads include induction motors, transformers, and reactors and they have a negative effect on the actual power used up by the loads. In this paper, Power factor correction (PFC) has been done by the addition of the needed capacitance to counteract the inductive load which is present in the electrical network of the Port Harcourt distribution system. The load values, MVAr values and the existing power factor of Port Harcourt electricity network where used to derive the needed shunt capacitance to a most appropriate value of 0.95. This enabled current savings of 23.15 percent in all the 11kV buses as well as reducing the required MVA needed to feed the loads to 101.48MVA as against 132.07MVA when the power factor was 0.73. These reductions were achieved by adding a capacitance of 34.48MVAr and the current reductions reduce losses along the lines since the square of current is proportional to losses. Also, the added system capacity will mean that more loads can be fed by the system when the added capacitance brings the system to a power factor of 0.95.

Downloads

Download data is not yet available.

References

Ackerman, P. Power Factor Correction for Power Systems Power Factor Correction for Power Systems.

Basu, S., & Bollen, M. H. (2005). A novel common power factor correction scheme for homes and offices. IEEE Transactions on Power Delivery, 20(3), 2257-2263.

Grainger, J. J. (1994). STEVENSON JR. WD:‘Power system analysis’.

Gross, C. A. (1986). Power system analysis (Vol. 1). New York: Wiley.

Inan, H., Khosravi, K., & Socher, R. (2016). Tying word vectors and word classifiers: A loss framework for language modeling. arXiv preprint arXiv:1611.01462.

Jiang, Y., Lee, F. C., Hua, G., & Tang, W. (1993, March). A novel single-phase power factor correction scheme. In Applied Power Electronics Conference and Exposition, 1993. APEC'93. Conference Proceedings 1993., Eighth Annual (pp. 287-292). IEEE.

Kersting, W. H. (2004, October). The computation of neutral and dirt currents and power losses. In Power Systems Conference and Exposition, 2004. IEEE PES (pp. 213-218). IEEE.

Meegahapola, L. G., Vittal, E., Keane, A., & Flynn, D. (2012, October). Voltage security constrained reactive power optimization incorporating wind generation. In Power System Technology (POWERCON), 2012 IEEE International Conference on (pp. 1-6). IEEE.

Saadat, H. (1999). Power system analysis (Vol. 232). Singapore: WCB/McGraw-Hill.

Thunberg, E., & Soder, L. (2000). On the estimation of harmonic power losses in distribution systems. In Harmonics and Quality of Power, 2000. Proceedings. Ninth International Conference on (Vol. 3, pp. 852-857). IEEE.

Published

2015-09-30

How to Cite

Eseosa, O., & Mik, K. (2015). Loss reduction in port harcourt 33/11kv distribution networks by power factor correction. International Research Journal of Management, IT and Social Sciences, 2(9), 10–17. Retrieved from https://sloap.org/journals/index.php/irjmis/article/view/318